Tag Registry
Fonte única de identidade para HMI, simulação, alarmes, histórico e futura reconciliação com PLC.
Visualização pública temporária da Planta D3. Comandos e alterações exigem autenticação.
Registro canônico de TAGs · 16 itens
SCHEMA 1.0| TAG | Tipo | Função | Unidade | Campo | Status | Observação |
|---|---|---|---|---|---|---|
| P01 | pump | Process pump 01 | — | — | RECONCILIATION_REQUIRED | Physical serial-to-P01 association not yet confirmed. |
| P02 | pump | Process pump 02 | — | — | RECONCILIATION_REQUIRED | Physical serial-to-P02 association not yet confirmed. |
| FCV-01 | control_valve | Cold-water flow control final element | % | FCV-1 | FIELD_CONFIRMED | KOSO ACV-103 family. Exact Cv/Kv/fail state/travel time still to validate. |
| FCV-02 | control_valve | Second flow-control final element | % | FCV-2 | FIELD_CONFIRMED | KOSO ACV-103; equal-percentage characteristic documented on field plate. |
| FIT-01 | flow_transmitter | Flow measurement loop 01 | L/h | FIT-01 | FIELD_CONFIRMED | Current configured range/calibration still to validate. |
| FIT-02 | flow_transmitter | Flow measurement loop 02 | L/h | FIT-02 | FIELD_CONFIRMED | Current configured range/calibration still to validate. |
| PIT-03 | pressure_transmitter | Pressure measurement loop 03 | kgf/cm²(g) | — | DOCUMENT_CONFIRMED | Current field instrument model/range/calibration still to validate. |
| LIT-01A | level_transmitter | Level measurement channel A | mm | — | DOCUMENT_CONFIRMED | Exact role relative to LIT-01B remains to validate. |
| LIT-01B | level_transmitter | Level measurement channel B | mm | — | DOCUMENT_CONFIRMED | Exact role relative to LIT-01A remains to validate. |
| TIT-01 | temperature_transmitter | Current field temperature transmitter | °C | TIT-01 | FIELD_CONFIRMED | Yokogawa transmitter; exact mapping to legacy TE/TT/TIC-05/06 requires reconciliation. |
| TV-01 | field_device | — | — | TV-01 | TO_VALIDATE | Physical device confirmed; exact functional role must not be inferred. |
| TV-02 | field_device | — | — | TV-02 | TO_VALIDATE | Physical device confirmed; exact functional role must not be inferred. |
| TV-03 | field_device | — | — | TV-03 | TO_VALIDATE | Physical device confirmed; exact functional role must not be inferred. |
| TV-04 | field_device | — | — | TV-04 | TO_VALIDATE | Physical device confirmed; exact functional role must not be inferred. |
| PCV-03 | control_valve | Pressure-control final element | % | PCV-01A | RECONCILIATION_REQUIRED | P&ID/field nomenclature conflict; do not collapse aliases until verified. |
| LCV-01 | control_valve | Level-control final element | % | LCV-03 | RECONCILIATION_REQUIRED | P&ID/field nomenclature conflict; preserve all aliases until verified. |